Thermal Interface Materials (TIM)
Master the critical layer between heat source and heat sink. Learn how TIMs fill microscopic gaps, compare TIM types, calculate thermal resistance, and apply installation best practices.
No matter how flat two surfaces appear, at the microscopic level they are rough. When a heat sink is placed on a component, actual metal-to-metal contact occurs at only 1-3% of the apparent surface area. The remaining 97-99% is filled with trapped air (k = 0.025 W/m·K) — an extremely poor thermal conductor.
A thermal interface material fills these microscopic voids, replacing the trapped air with a medium that has 40-320× higher thermal conductivity. This can reduce interface resistance by 5-20×.
Interactive: Gap-Fill Visualization
Move the slider to see how TIM progressively fills the microscopic air gaps between two mating surfaces, replacing insulating air with a conductive medium.
| TIM Type | Conductivity (W/m·K) | Typical BLT (μm) | Advantages | Limitations |
|---|---|---|---|---|
| Thermal Grease | 1 - 5 | 25 - 75 | Lowest thermal resistance, no curing, reworkable | Pump-out over thermal cycles, messy application |
| Thermal Pads | 1 - 6 | 200 - 2000 | Easy handling, gap filling, electrically insulating options | Higher resistance due to thickness, limited compression |
| Phase-Change Materials | 3 - 8 | 20 - 50 | Thin BLT at operating temp, no pump-out, long life | Requires initial heat cycle to activate, moderate cost |
| Gap Fillers | 1 - 3 | 500 - 5000 | Bridges large gaps, conformable, vibration dampening | High thermal resistance due to thickness, low conductivity |
Enter contact area and power, then compare thermal resistance and temperature drop for several TIM options.
This plot shows how thermal resistance increases with bond line thickness for five representative TIM types, assuming a 400 mm² contact area. Note the log-log scale — resistance scales linearly with BLT but conductivity shifts the entire curve.
Log-log plot: Bond Line Thickness (10-2000 μm) vs Thermal Resistance (°C/W), 400 mm² area.
Clean both surfaces with isopropyl alcohol (IPA) to remove oils, dust, and old TIM residue. Surface roughness should be <10μm Ra for grease.
For grease, apply a thin center dot or X-pattern. Excess grease increases BLT and acts as an insulator, not a conductor.
Use spring-loaded fasteners with specified torque. Uneven pressure degrades thermal performance by 20-50%.
Lower heatsinks from one edge to sweep air outward. Never drop straight down.
Grease can pump out after 500-2000 cycles. For >10 year life, prefer phase-change materials or cured adhesives.
Use ceramic-filled pads (alumina/boron nitride) rather than grease. Verify breakdown voltage exceeds system voltage by 2×.